Piston Reaction to Varying Differential Pressures
Below the AutoFlow Control Range
with ATC Modulating Flow

 

Within the AutoFlow Control Range
with ATC Wide Open

 

Above the AutoFlow Control Range
with ATC Wide Open

 

 
Time-tested, innovative solutions deliver leak-proofed guaranteed performance for commercial, industrial and residential applications.
 
Flow Design is ISO 9001 Certified, is an active ASHRAE member, and is a leader in testing laboratory ratings.
 
© Copyright 2006, Flow Design, Inc.

The differential pressure is below the minimum needed to activate the AutoFlow piston. It is fully extended and acts as a fixed orifice with a Cv of .71 times design flow (2-32 range) or .45 times design flow (5-60 range). The ATC is controlling the GPM in this zone.

AutoFlow piston now responds to changes in differential pressure by repositioning the variable side orifices to maintain design flow ±five percent. At approximately 50 percent of control range, the consolidated side port now handles all flow through the variable orifice. The Cv is variable in this range and is a function of piston position.

Now fully retracted, only the AutoFlow piston’s end port is exposed. The regulator functions as a fixed orifice and will react to increased pressure differential with increased flow in accordance with the formula: GPM = Cv &P. Fixed Cv of the valve is now 18 times design flow (2-32 range) and 13 times design flow (5-60 range). A 25 percent “over range” (32 psi to 40 psi) increases the flow by only 12 percent!