Selecting the Proper AutoFlow Valve
2
Review Your
Piping Schematic

Make sure the detail reflects the following:

  • The balancing valve is on the return side of the coil. It should be located just before the exit isolation valve.
  • A Y-strainer with a blowdown valve located on the coil inlet.
  • Adequate unions, P/T ports and air venting.
Terminal Unit - No ATC

Features : Y-strainer with blowdown, AutoFlow on the return

Terminal Unit - Two-way ATC on Return

Features: Y-strainer with blowdown, AutoFlow on the return

Terminal Unit - Two-way ATC on Supply

Features: Y-strainer with blowdown, AutoFlow on the return

Heat Pump - No ATC

Features: Fire rated hoses,Y-strainer with blowdown, AutoFlow on the return

Terminal Unit - Three-way Mixing ATC

Features: ATC normally closed to coil, Y-strainer with blowdown, AutoFlow on the return

Multiple Coils - Three-way Mixing ATC

Features: Y-strainer with blowdown, AutoFlow on the return, manual balance valves on individual coils

Air Handler with Secondary Pump

Features: Pump on the supply, Y-strainer with blowdown, AutoFlow on the return

Secondary System Pumps in Parallel

Can be staged for required flow.

By-pass Line Allows Flow Either Direction
Primary Pumping Through
Chiller, Boiler or Cooling Tower

Use WS series to 30" to prevent overflow through chillers, etc.

 